5-52 750/760 Feeder Management Relay GE Multilin5.6 S5 PROTECTION 5 SETPOINTS5b) SENSITIVE GROUND TIME OCPATH: SETPOINTS ÖØ S5 PROTECTION ÖØ SENSTV GND CURRENT Ö SENSTV GND TIME OCThe sensitive ground time overcurrent element, ANSI device 51SG is programmed in this subgroup.Figure 5–18: SENSITIVE GROUND TOC LOGIC SENSTV GND TIME OC [ENTER] for moreSENSTV GND TIME OCFUNCTION: DisabledRange: Disabled, Trip, Trip & AR, Alarm, Latched Alarm,ControlSENSTV GND TIME OCRELAYS (3-7): -----Range: Any combination of 3 to 7 Auxiliary relaysSENSTV GND TIME OCPICKUP: 1.00 x CTRange: 0.05 to 20.00 x CT in steps of 0.01SENSTV GND TIME OCCURVE: Ext. InverseRange: see Table 5–4: TOC Curve Selections on page5–32 for valuesSENSTV GND TIME OCMULTIPLIER: 1.00Range: 0.00 to 100.00 in steps of 0.01SENSTV GND TIME OCRESET: InstantaneousRange: Instantaneous, LinearSENSTV GND TIME OCDIRECTION: DisabledRange: Disabled, Forward, ReverseENTERESCAPEð ðMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPE