5-70 750/760 Feeder Management Relay GE Multilin5.6 S5 PROTECTION 5 SETPOINTS5c) FREQUENCY DECAYPATH: SETPOINTS ÖØ S5 PROTECTION ÖØ FREQ ÖØ FREQ DECAYThere is one frequency decay protection element, ANSI device 81D which can provide a faster response to system distur-bances than the underfrequency elements. See the previous section for descriptions of the MIN OPERATING CURRENT andMIN OPERATING VOLTAGE setpoints.Figure 5–33: FREQUENCY DECAY LOGIC FREQ DECAY [ENTER] for moreFREQ DECAYFUNCTION: DisabledRange: Disabled, Trip, Alarm, Latched Alarm, ControlFREQ DECAYRELAYS (3-7): -----Range: Any combination of 3 to 7 Auxiliary relaysSee 5.6.1: Overview on page 5–32 for details.FREQ DECAYRATE: 1.0 Hz/sRange: 0.1 to 5.0 Hz/s in steps of 0.1FREQ DECAYPICKUP: 59.00 HzRange: 20.00 to 65.00 Hz in steps of 0.01See 5.6.1: Overview on page 5–32 for details.FREQ DECAYDELAY: 2.00 sRange: 0.00 to 600.00 s in steps of 0.01See 5.6.1: Overview on page 5–32 for details.MIN OPERATINGVOLTAGE: 0.70 x VTRange: 0.00 to 1.25 x VT in steps of 0.01MIN OPERATINGCURRENT: 0.00 x CTRange: 0.00 to 1.25 x CT in steps of 0.01ENTERESCAPEð ðMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPE