GE Multilin 750/760 Feeder Management Relay 5-155 SETPOINTS 5.2 S1 RELAY SETUP55. Continue entering characters and spaces until the desired message is displayed. If a character is entered incorrectly,repeatedly press the key until the cursor returns to the position of the error and enter the correct character. Youmay also press the and keys to restart the editing process.6. Press the or key when editing is complete. To select this message as a default message, followthe instructions in the section on adding default messages.5.2.10 CLEAR DATAPATH: SETPOINTS Ö S1 RELAY SETUP ÖØ CLEAR DATAThese setpoints are used to clear specific memory functions after the data has been read by an operator. The CLEARENERGY USE setpoint clears all accumulated power consumption data and updates the ENERGY USE DATA LAST RESET date.The CLEAR MAX DMND setpoint clears all maximum demand data values and updates the DMND DATA LAST RESET date.The event recorder saves the most recent 128 events, automatically overwriting the oldest event. The CLEAR EVENTRECORDER setpoint clears all recorded event data and updates the EVENT RECORDER LAST RESET date.5.2.11 INSTALLATIONPATH: SETPOINTS Ö S1 RELAY SETUP ÖØ INSTALLATIONThe Relay Not Ready self-test warning message will be displayed until S1 RELAY SETUP ÖØ INSTALLATION Ö 760OPERATION is set to "Ready". This warns against the installation of a relay whose setpoints have not been enteredfor the required application. This setpoint is defaulted to "Not Ready" when the relay leaves the factory.These setpoints should be used on a new installation or after new equipment has been installed.The RESET TRIP COUNTER DATA setpoint clears all accumulated trip counter values and updates the TRIP COUNTERS LASTRESET date. The RESET ARCING CURRENT setpoint clears all arcing current data values and updates the ARCING CURRENTLAST RESET date.The RESET AR COUNT DATA setpoint clears the autoreclose shot count value and updates the AR SHOT COUNT LAST RESETdate. The RESET AR RATE DATA setpoint clears the autoreclose shot rate value and updates the ARCING CURRENT LASTRESET date. These two setpoints are applicable to the 760 only. CLEAR DATA [ENTER] for moreCLEAR ENERGY USEDATA? NoRange: Yes, NoCLEAR MAX DMNDDATA? NoRange: Yes, NoCLEAR EVENT RECORDERDATA: NoRange: Yes, No INSTALLATION [ENTER] for more760 OPERATION:Not ReadyRange: Ready, Not ReadySetpoint reads 750 OPERATION for 750 relaysRESET TRIP COUNTERDATA? NoRange: Yes, NoRESET ARCING CURRENTDATA? NoRange: Yes, NoRESET AR COUNTDATA? NoRange: Yes, NoMessage is only seen in 760 relays.RESET AR RATEDATA? NoRange: Yes, NoMessage is only seen in 760 relays.ENTERESCAPE ENTERMESSAGE MESSAGEENTERESCAPEð ðMESSAGEESCAPEMESSAGEESCAPEENTERESCAPEð ðMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEWARNING