5-122 750/760 Feeder Management Relay GE Multilin5.8 S7 CONTROL 5 SETPOINTS5c) AUTORECLOSE RATE SUPERVISIONPATH: SETPOINTS ÖØ S7 CONTROL ÖØ AR ÖØ RATE SUPERVISIONThe autoreclose rate supervision feature monitors the number of recloses per hour. Once the number of recloses withinone hour exceeds the MAX AR RATE setpoint, the autoreclose scheme is sent to lockout.Figure 5–74: AUTORECLOSE RATE SUPERVISION LOGICd) AUTORECLOSE CURRENT SUPERVISIONPATH: SETPOINTS ÖØ S7 CONTROL ÖØ AR ÖØ CURRENT SUPERVISION RATE SUPERVISION [ENTER] for moreRATE SUPERVISIONFUNCTION: DisabledRange: Disabled, Alarm, Latched Alarm, ControlRATE SUPERVISIONRELAYS (3-7): -----Range: Any combination of the 3 to 7 Auxiliary relaysMAX ARRATE: 25 /hr.Range: 1 to 50/hr. in steps of 1 CURRENT SUPERVISION [ENTER] for moreCURRENT SUPERVISIONFUNCTION: DisabledRange: Enabled, Disabled3 SHOTS FOR CURRENTABOVE: 17.00 x CTRange: 0.00 to 20.00 x CT in steps of 0.012 SHOTS FOR CURRENTABOVE: 18.00 x CTRange: 0.00 to 20.00 x CT in steps of 0.011 SHOTS FOR CURRENTABOVE: 19.00 x CTRange: 0.00 to 20.00 x CT in steps of 0.01CURRENT SUPERVISIONTO LOCKOUT: DisabledRange: Enabled, DisabledLOCKOUT FOR CURRENTABOVE: 20.00 x CTRange: 0.00 to 20.00 x CT in steps of 0.01ENTERESCAPEð ðMESSAGEESCAPEMESSAGEESCAPEENTERESCAPEð ðMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPE