CHAPTER 5: SETTINGS PRODUCT SETUPL90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-375Number of DecimalsRange: 0 to 10 in steps of 1Default: 3This setting specifies the number of decimal places in the displayed metered value.5.3.3.4 Single-line diagram editorThe path is Settings > Product Setup > Graphical Panel > Single Line Diagram Editor. Use is explained in the Interfaceschapter.5.3.3.5 Annunciator editorThe annunciator editor is used to create annunciator content for the graphical front panel, including alarms and actualvalues. Use is explained in the Interfaces chapter.The path is Settings > Product Setup > Graphical Panel > Annunciator Editor.To add an alarm, access the Annunciator Editor, configure the layout and page name, configure the alarm, set the text andcolor, then save. On the graphical front panel, view the alarm by pressing the Annunciator Tab pushbutton at the bottomof the Home page. (Alarms do not display automatically.) Acknowledge or reset the alarm by navigating to it with the arrowpushbuttons, then press the ENTER or RESET pushbutton.The figure shows alarms for basic functions. The last annunciator page is named Device Alarms. Alarms are set for thedevice being offline, Ethernet issues, unauthorized access, battery failure, and high ambient temperature. They can resetthemselves when conditions return to normal, except for unauthorized access and temperature monitoring, which requirethe alarms to be acknowledged. The self-test error functions have also been enabled under Settings > Product Setup >User-Programmable Self Tests (not shown). When the alarms are triggered, they display with a red background. An alarmis acknowledged by using the arrow keys on the graphical front panel then pressing the Enter button.