5-196 L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUALFLEXLOGIC CHAPTER 5: SETTINGS5ELEMENT:Phase directionalovercurrentPH DIR1 BLK APH DIR1 BLK BPH DIR1 BLK CPH DIR1 BLKPhase A directional 1 blockPhase B directional 1 blockPhase C directional 1 blockPhase directional 1 blockPH DIR2 Same set of operands as shown for PH DIR1ELEMENT:Phase distancePH DIST Z1 PKPPH DIST Z1 OPPH DIST Z1 OP ABPH DIST Z1 OP BCPH DIST Z1 OP CAPH DIST Z1 PKP ABPH DIST Z1 PKP BCPH DIST Z1 PKP CAPH DIST Z1 SUPN IABPH DIST Z1 SUPN IBCPH DIST Z1 SUPN ICAPH DIST Z1 DPO ABPH DIST Z1 DPO BCPH DIST Z1 DPO CAPhase distance zone 1 has picked upPhase distance zone 1 has operatedPhase distance zone 1 phase AB has operatedPhase distance zone 1 phase BC has operatedPhase distance zone 1 phase CA has operatedPhase distance zone 1 phase AB has picked upPhase distance zone 1 phase BC has picked upPhase distance zone 1 phase CA has picked upPhase distance zone 1 phase AB IOC is supervisingPhase distance zone 1 phase BC IOC is supervisingPhase distance zone 1 phase CA IOC is supervisingPhase distance zone 1 phase AB has dropped outPhase distance zone 1 phase BC has dropped outPhase distance zone 1 phase CA has dropped outPH DIST Z2 to 5 Same set of operands as shown for PH DIST Z1ELEMENT:Phase instantaneousovercurrentPHASE IOC1 PKPPHASE IOC1 OPPHASE IOC1 DPOPHASE IOC1 PKP APHASE IOC1 PKP BPHASE IOC1 PKP CPHASE IOC1 OP APHASE IOC1 OP BPHASE IOC1 OP CPHASE IOC1 DPO APHASE IOC1 DPO BPHASE IOC1 DPO CAt least one phase of phase instantaneous overcurrent 1 has picked upAt least one phase of phase instantaneous overcurrent 1 has operatedAll phases of phase instantaneous overcurrent 1 have dropped outPhase A of phase instantaneous overcurrent 1 has picked upPhase B of phase instantaneous overcurrent 1 has picked upPhase C of phase instantaneous overcurrent 1 has picked upPhase A of phase instantaneous overcurrent 1 has operatedPhase B of phase instantaneous overcurrent 1 has operatedPhase C of phase instantaneous overcurrent 1 has operatedPhase A of phase instantaneous overcurrent 1 has dropped outPhase B of phase instantaneous overcurrent 1 has dropped outPhase C of phase instantaneous overcurrent 1 has dropped outPHASE IOC2 to 12 Same set of operands as shown for PHASE IOC1ELEMENT:Phase overvoltagePHASE OV1 PKPPHASE OV1 OPPHASE OV1 DPOPHASE OV1 PKP APHASE OV1 PKP BPHASE OV1 PKP CPHASE OV1 OP APHASE OV1 OP BPHASE OV1 OP CPHASE OV1 DPO APHASE OV1 DPO BPHASE OV1 DPO CAt least one phase of overvoltage 1 has picked upAt least one phase of overvoltage 1 has operatedAll phases of overvoltage 1 have dropped outPhase A of overvoltage 1 has picked upPhase B of overvoltage 1 has picked upPhase C of overvoltage 1 has picked upPhase A of overvoltage 1 has operatedPhase B of overvoltage 1 has operatedPhase C of overvoltage 1 has operatedPhase A of overvoltage 1 has dropped outPhase B of overvoltage 1 has dropped outPhase C of overvoltage 1 has dropped outPHASE OV2 to 3 Same set of operands as shown for PHASE OV1ELEMENT:Phase selectPHASE SELECT AGPHASE SELECT BGPHASE SELECT CGPHASE SELECT ABPHASE SELECT BCPHASE SELECT CAPHASE SELECT ABGPHASE SELECT BCGPHASE SELECT CAGPHASE SELECT 3PPHASE SELECT SLGPHASE SELECT MULTI-PPHASE SELECT VOIDPhase A to ground fault is detectedPhase B to ground fault is detectedPhase C to ground fault is detectedPhase A to B fault is detectedPhase B to C fault is detectedPhase C to A fault is detectedPhase A to B to ground fault is detectedPhase B to C to ground fault is detectedPhase C to A to ground fault is detectedThree-phase symmetrical fault is detectedSingle line to ground fault is detectedMulti-phase fault is detectedFault type cannot be detectedOperand type Operand syntax Operand description