5-54 L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUALPRODUCT SETUP CHAPTER 5: SETTINGS5 DNP VOLTAGE SCALEFACTOR: 1Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,100000, 1000000, 10000000, 100000000 DNP POWER SCALEFACTOR: 1Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,100000, 1000000, 10000000, 100000000 DNP ENERGY SCALEFACTOR: 1Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,100000, 1000000, 10000000, 100000000 DNP PF SCALEFACTOR: 1Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,100000, 1000000, 10000000, 100000000 DNP OTHER SCALEFACTOR: 1Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,100000, 1000000, 10000000, 100000000 DNP CURRENT DEFAULTDEADBAND: 30000Range: 0 to 100000000 in steps of 1 DNP VOLTAGE DEFAULTDEADBAND: 30000Range: 0 to 100000000 in steps of 1 DNP POWER DEFAULTDEADBAND: 30000Range: 0 to 100000000 in steps of 1 DNP ENERGY DEFAULTDEADBAND: 30000Range: 0 to 100000000 in steps of 1 DNP PF DEFAULTDEADBAND: 30000Range: 0 to 100000000 in steps of 1 DNP OTHER DEFAULTDEADBAND: 30000Range: 0 to 100000000 in steps of 1 DNP TIME SYNC IINPERIOD: 1440 minRange: 1 to 10080 min. in steps of 1 DNP MESSAGE FRAGMENTSIZE: 240Range: 30 to 2048 in steps of 1 DNP OBJECT 1DEFAULT VARIATION: 2Range: 1, 2 DNP OBJECT 2DEFAULT VARIATION: 2Range: 1, 2, 3 DNP OBJECT 20DEFAULT VARIATION: 1Range: 1, 2, 5, 6 DNP OBJECT 21DEFAULT VARIATION: 1Range: 1, 2, 9, 10 DNP OBJECT 22DEFAULT VARIATION: 1Range: 1, 2, 5, 6 DNP OBJECT 23DEFAULT VARIATION: 1Range: 1, 2, 5, 6 DNP OBJECT 30DEFAULT VARIATION: 1Range: 1, 2, 3, 4, 5 DNP OBJECT 32DEFAULT VARIATION: 1Range: 1, 2, 3, 4, 5, 7 DNP NUMBER OF PAIREDCONTROL POINTS: 0Range: 0 to 32 in steps of 1 DNP TCP CONNECTIONTIMEOUT: 120 sRange: 10 to 7200 s in steps of 1 DNP EVENT TIME BASE:LOCALRange: UTC, LOCAL