GE Multilin L90 Line Current Differential System 5-2735 SETTINGS 5.8 INPUTS/OUTPUTS5The GOOSE analog input FlexAnalog™ values are available for use in other L90 functions that use FlexAnalog™ values.5.8.12 IEC 61850 GOOSE INTEGERSPATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ IEC 61850 GOOSE UINTEGERS ÖØ GOOSE UINTEGER INPUT 1(16)The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger™ values between any two UR-series devices. The following settings are available for each GOOSE uinteger input.• UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device isoffline and the UINTEGER 1 DEFAULT MODE is set to “Default Value”.This setting is stored as a 32-bit unsigned integernumber.• UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of theGOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is“Default Value”, then the value of the GOOSE uinteger input is defined by the UINTEGER 1 DEFAULT setting.The GOOSE integer input FlexInteger™ values are available for use in other L90 functions that use FlexInteger™ values.Table 5–24: GOOSE ANALOG INPUT BASE UNITSELEMENT BASE UNITS87L SIGNALS(Local IA Mag, IB, and IC)(Diff Curr IA Mag, IB, and IC)(Terminal 1 IA Mag, IB, and IC)(Terminal 2 IA Mag, IB and IC)IBASE = maximum primary RMS value of the +IN and –IN inputs(CT primary for source currents, and 87L source primary current for line differential currents)87L SIGNALS(Op Square Curr IA, IB, and IC)(Rest Square Curr IA, IB, and IC)BASE = Squared CT secondary of the 87L sourceBREAKER ARCING AMPS(Brk X Arc Amp A, B, and C) BASE = 2000 kA 2 × cycledcmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configuredunder the +IN and –IN inputs.FREQUENCY fBASE = 1 HzPHASE ANGLE ϕBASE = 360 degrees (see the UR angle referencing convention)POWER FACTOR PF BASE = 1.00RTDs BASE = 100°CSOURCE CURRENT I BASE = maximum nominal primary RMS value of the +IN and –IN inputsSOURCE ENERGY(Positive and Negative Watthours,Positive and Negative Varhours)EBASE = 10000 MWh or MVAh, respectivelySOURCE POWER PBASE = maximum value of V BASE × I BASE for the +IN and –IN inputsSOURCE VOLTAGE VBASE = maximum nominal primary RMS value of the +IN and –IN inputsSYNCHROCHECK(Max Delta Volts)VBASE = maximum primary RMS value of all the sources related to the +IN and –IN inputs GOOSE UINTEGER INPUT 1UINTEGER 1 DEFAULT:1000Range: 0 to 429496295 in steps of 1MESSAGE UINTEGER 1 DEFAULTMODE: Default ValueRange: Default Value, Last Known