5-50 F35 Multiple Feeder Protection System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5The GGIO1 status configuration points are shown below:PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GGIO1 STATUS CONFIGURATIONThe NUMBER OF STATUS POINTS IN GGIO1 setting specifies the number of “Ind” (single point status indications) that areinstantiated in the GGIO1 logical node. Changes to the NUMBER OF STATUS POINTS IN GGIO1 setting will not take effect untilthe F35 is restarted.The GGIO2 control configuration points are shown below:PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GGIO2 CONTROL CONFIGURATION GGIO2 CF SPSCO 1(64)The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0”(status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the F35virtual inputs.The GGIO4 analog configuration points are shown below:PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GGIO4 ANALOG CONFIGURATIONThe NUMBER OF ANALOG POINTS setting determines how many analog data points will exist in GGIO4. When this value ischanged, the F35 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newlyconfigured number of analog points. GGIO1 STATUS CONFIGURATIONNUMBER OF STATUSPOINTS IN GGIO1: 8Range: 8 to 128 in steps of 8MESSAGE GGIO1 INDICATION 1OffRange: FlexLogic operandMESSAGE GGIO1 INDICATION 2OffRange: FlexLogic operandMESSAGE GGIO1 INDICATION 3OffRange: FlexLogic operand↓MESSAGE GGIO1 INDICATION 128OffRange: FlexLogic operand GGIO2 CF SPCSO 1GGIO2 CF SPCSO 1CTLMODEL: 1Range: 0, 1, or 2 GGIO4 ANALOG CONFIGURATIONNUMBER OF ANALOGPOINTS IN GGIO4: 8Range: 4 to 32 in steps of 4MESSAGE GGIO4 ANALOG 1 MEASURED VALUEMESSAGE GGIO4 ANALOG 2 MEASURED VALUEMESSAGE GGIO4 ANALOG 3 MEASURED VALUE↓MESSAGE GGIO4 ANALOG 32 MEASURED VALUE