GE Multilin F35 Multiple Feeder Protection System 6-236 ACTUAL VALUES 6.3 METERING66.3.4 FLEXELEMENTS™PATH: ACTUAL VALUES METERING FLEXELEMENTS FLEXELEMENT 1(16)The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.6.3.5 IEC 61580 GOOSE ANALOG VALUESPATH: ACTUAL VALUES METERING IEC 61850 GOOSE ANALOGSThe F35 Multiple Feeder Protection System is provided with optional IEC 61850 communications capabil-ity. This feature is specified as a software option at the time of ordering. Refer to the Ordering section ofchapter 2 for additional details.The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are receivedvia IEC 61850 GOOSE messages sent from other devices. FLEXELEMENT 1FLEXELEMENT 1OpSig: 0.000 puTable 6–2: FLEXELEMENT BASE UNITSDCmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configuredunder the +IN and –IN inputs.FAULT LOCATION BASE = Line Length as specified in Fault ReportFREQUENCY fBASE = 1 HzPHASE ANGLE ϕBASE = 360 degrees (see the UR angle referencing convention)POWER FACTOR PF BASE = 1.00RTDs BASE = 100°CSOURCE CURRENT I BASE = maximum nominal primary RMS value of the +IN and –IN inputsSOURCE ENERGY(Positive and Negative Watthours,Positive and Negative Varhours)EBASE = 10000 MWh or MVAh, respectivelySOURCE POWER PBASE = maximum value of V BASE × IBASE for the +IN and –IN inputsSOURCE VOLTAGE VBASE = maximum nominal primary RMS value of the +IN and –IN inputs IEC 61850 GOOSE ANALOGSANALOG INPUT 10.000MESSAGE ANALOG INPUT 20.000MESSAGE ANALOG INPUT 30.000↓MESSAGE ANALOG INPUT 320.000