25Installation height shall be less than 280mm.There should be a right angle with unit, 300mm from unit.300mm below 1~1.5mClamp(accessorry)Over 100Drain hose(accessory) drain water lifting pipeSuspending bracket self-provided stiff pipe75 below500 below(accessory)Connect water hoseswith at joint.Electric control box220 280 below500 below⑥ Installation of Waterdrainage Pipe(1) Install water drainage pipe• Pipe dia, shall be equal or larger than that of unit piping. (Pipe of polyethylent; size 25mm; O.D 32mm)• Drain pipe should be short, with a downward slope at least 1/100 toprevent air bag from happening.• If downward slope can t be made, take other measures to lift it up.• Keep a distance of 1-1.5m between suspending brackets, tomake water hose straight.• Use the self-provided stiff pipe and clamp ① with unit. Insert water pipe into water plug until it reaches the whitetape. Tighten the clip until head of the screw is less than 4mm from hose.• Wind the drain hose to the clip using seal pad ⑨ .• Insulate drain hose in the room.Tape (White)ClampSelf-provided stiff pipeClampLarge size seal pad(accessory)4mm below(accessory)Liquid pipeTape (White)ClampSelf-provided stiff pipeClampLarge size seal pad(accessory)4mm below(accessory)