70Item Model AD140S2SM3FA/1UH140P1ERKFunction Cooling HeatingCapacity kW 13.4(3.5~15.0) 15.5(4~19.0)Sensible heat ratio 0.74Total power input kW 4.05(1.0-6.5) 4.18(1.0-6.5)Max. power input W 6500 6500EER or COP W/W 3.31(A) 3.70(A)Dehumidifying capacity 10 -3×m3/h 4.9Power cable /Power source N, V, Hz 3N~380-415V,50/60HzRunning/Max. Running current A/A 7.0(2.9-11.0)/11A 7.3(2.9-11.0)/11AStart current A /Circuit breaker AIndoor unitUnit model (color) AD140S2SM3FAFanType×Number CENTRIFUGALX3Speed (H-M-L) r/min 1180/1080/990/930Fan motor output/ input power kW 0.285Air-flow (H-M-L) kW 0.200External static pressure m 3/h 2500/2160/1780/1500(25/37(default)/50/70/90/100/110/120/130/150Pa)HeatexchangerType/Diameter mm Inner grooved pipe/φ7.0Total area m2 /Dimension External (L×W×H) mm×mm×mm 1500*700*248Package (L×W×H) mm×mm×mm 1710/870/330Drainage pipe (material, I.D./O.D.) mm PVC 21/25Controller (O-Optional, S-Standard) Wired YR-E17(S)Infrared YR-HBS01(O)Fresh air hole dimension mm 123Electricity heater kW 0Sound power noise level (H-M-L) dB (A) 66Sound pressure noise level (H-M-L) dB (A) 46/43/38Weight (Net / Shipping) kg / kg 52/62PipingRefrigerant Type / Charge g R410A/3700Recharge quantity g/m 45Pipe Liquid mm 9.52Gas mm 15.88Between I.D&O.DMAX.Drop m 30MAX.Piping length m 75Norminal condition:Indoor temperature (cooling): 27°C DB/19°C WB, indoor temperature (heating): 20°C DBOutdoor temperature (cooling): 35°C DB/24°C WB, outdoor temperature (heating): 7°C DB/6°C WBThe noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensitymeter. It is a sound pressure noise level.