IDS 816 700-283-02I Issued September 2009 187. If you do not wish to change the data within this sub-location, press the [#] hash key. TheREADY indicator will continue flashing and the AWAY indicator will turn off.8. Repeat steps 4 to 7 until all sub-locations at the current location have been programmed asrequired.9. Press the hash [#] key to exit from the current location, the ARMED LED will turn off and theREADY indicator will continue flashing.10. Repeat steps 2 to 9 until all locations, and their sub-locations, have been programmed asrequired.11. Press the [#] hash key again to exit from program mode (READY LED will stop flashing).7.4 Programming a Bitmapped Location1. A bitmapped location allows the installer to program multiple panel features within a singlelocation or sub-location. This is achieved using the individual zone LED’s to indicate whichfeatures are enabled or disabled.2. By referring to the appropriate location reference tables, the installer can view the entire selectionof features associated with that location.3. A zone LED that is on indicates that a feature is enabled. A LED that is off indicates that a featureis disabled.4. The installer is able to toggle a selected LED indicator ON or OFF by entering the correspondingnumber followed by the [*] star key5. Once a complete selection of features has been finalised, press the [#] key to leave thelocation/sub-location with the state as indicated by the LED.Example:Location 40 allows the installer to select up to twelve trouble conditions which may be displayed. Bydefault, only AC fail and low battery trouble conditions are enabled.Entering program mode and viewing the contents of Location 40 it will be noted that the zone 1and zone 5 LED’s will be on. All other zone LED indicators will be turn off.To enable the Comms Fail Trouble Display (indicated by zone 2 LED) press the [2] keyfollowed by the [*] star key. A long beep will indicate a valid entry and the zone 2 LED will come onindicating that Comms Fail Trouble Display has been enabled.Continue selection (or de-selection) of the desired trouble conditions. Once a final selectionhas been made press the [#] hash key to exit the location. The AWAY indicator will turn off and a longbeep will indicate acceptance of a valid data entry.7.5 Incorrect Data Entries1. When programming either standard or extended locations any attempt to enter invalid data willresult in an error beep (3 short beeps)2. In the case of standard locations, the AWAY indicator will remain on after the error beeps. Re-enter the correct data. There is no need to press the [#] hash key.3. In the case of extended locations, the AWAY and ARMED indicators will remain on after the errorbeeps. Re-enter the correct data. There is no need to press the [#] key.7.6 Programming Location SummaryA detailed description of each location and its options follows.