155The per phase induction motor stator resistance in ohms. Thisparameter is only available for induction motors.For PM motors this parameter is not required and therefore is notvisible.The equivalent induction motor sigma inductance. This value iscalculated from the per phase stator and rotor leakage inductances.This parameter is only available for induction motors.For PM motors this parameter is not required and therefore is notvisible.This is the per phase induction motor rotor resistance. Thisparameter is only available for induction motors.For PM motors this parameter is not required and therefore is notvisible.This is the per phase induction motor magnetizing inductance. Thisparameter is only available for induction motors. The magnetizinginductance can be monitored in parameter ru.87. If the actualmagnetizing current is too high lower this inductance value in stepsof 20. If it is too low, raise the value.This parameter activates various controllers in the drive. Eachfunction is binary weighted as listed below. The sum of the thesevalues determines which are on or off.1 = Motor model control observer active2 = Rotor resistance temperature adaptation8 = Maximum output voltage regulation (max 110%)32 = Active fl ux control128 = Flux proofi ngAfter the auto tuning process the motor model control observeris automatically turned on. If for any reason the auto tuningprocess did not provide the desired control, the function cansimply be turned off by setting this parameter to 8.Ld.20Stator resistanceLd.21Sigma inductanceLd.22Rotor resistanceLd.23Magnetizing inductanceLd.24Motor controliAdvanced Drive DataIMPMIMPMIMPM