223.4 Adjusting ParametersAll equipment is shipped from the factory fully checked and adjusted based on the customer order. Do notmake any adjustments unless the equipment has been powered-up and the settings have been determined tobe incorrect. If the settings have been determined to be incorrect, adjustments may be made as detailed below.Refer to page # for TPSD control menu structure flow chart.3.4.1 Settings MenuIn the Settings Menu the customer can access and change various parameters used by the TPSD. To access theSettings Menu, press the MENU button, select “Settings Menu” and press the ENTER button.Once in the settings menu the customer can navigate the menus with the up and down arrows. To enter asubmenu use the ENTER button. The BACK button returns to the previous menu. When making a selection,the ENTER button will store the value and step back. The BACK button will not save the change and will go astep back. At any point the settings menu can be exited, with or without saving the settings.The settings menu is divided into six submenus: “Float/Eq Voltage”, “Equalize Timer Settings”, “Alarm Settings”,“Ground Detection Alarm”, “Temperature Comp Settings”, “Communication Settings”, and “LCD Settings”.Return to DefaultsThe first option in the settings menu is “Return to Defaults”. This option resets all customer adjustable settingsto the factory defaults. It is important to note that the factory defaults, are not necessarily the correct settingsfor the specific DC system. Before the charger is shipped, adjustments are made at the factory using the samecalibration procedure. If the charger is reset to default these factory changes may be reset.Ex: The softwaredefault for a 130V charger is based on 60 lead cells, a 63L charger is factory adjusted for a higher voltage.Returning to default will return the charger to a 60L voltage setting.3.4.1.1. Float/Eq VoltageThe Float/Eq Voltage submenu provides access to change the Float Voltage and Equalize Voltage Settings.Float Voltage SettingThe float voltage adjustment is set at the factory at 2.17 V/C (LA), 2.25 V/C (VRLA) or 1.4 V/C (NC). The floatvoltage increments by 0.1V. Select “Float Voltage Setting” and press then ENTER button. Press the UP and/orDOWN buttons until the required voltage level is displayed. Press ENTER to store the setting or BACK to cancel.The approximate adjustable range is as follows:2.02 – 2.40 V/C (LA) (VRLA)1.29 – 1.55 V/C (NC)Equalize Voltage SettingThe equalize voltage adjustment is set at the factory at 2.33 V/C (LA), 2.27 V/C (VRLA) or 1.55 V/C (NC). Theequalize voltage increments by 0.1V. Select “Equalize Voltage Setting” and press then ENTER button. Press theUP and/or DOWN buttons until the desired voltage is displayed. Press ENTER to store the setting, BACK tocancel.< Return to >Defaults< Float >Voltage Setting Float Voltage130.2V< Equalize >Voltage Setting Equalize Voltage139.8V