253.4.1.5. Communications SettingsThe communication settings menu changes depending on the type of communication protocol used in the unit.For details on connection instructions as well as operation instructions refer to the Scada Interface instruction manualincluded with the unit.3.4.1.5.1 Units with DNP 3.0 Communication Protocol (Option 21P).Setting -> Default setting (Selection)DNP Node Address -> 0004DNP Port Type -> RS485 (RS485, RS232)DNP Parity Type -> None (None, ADD, EVEN)DNP Baud Rate -> 9600 (1200, 2400, 4800, 9600, 19200, 38400)DNP IP Address -> 192.168.000.006DNP Subnet Mask -> 255.255.255.000DNP Gateway -> 192.168.000.001DNP TCP Port Number -> 20000Read Only Mode -> No (No, Yes)3.4.1.5.2 Units with NODBUS (Option 21Q)Setting -> Default setting (Selection)Modbus Type -> TCP (TCP, Serial)Modbus Address -> 1 (1 – 247)Modbus Baud Rate -> 9600 (1200, 2400, 4800, 9600, 19200, 38400)(Setting available only if Modbus Type is set to Serial)Modbus Parity Type -> None (None, ADD, EVEN)(Setting available only if Modbus Type is set to Serial)Read Only Mode -> No (No, Yes)For TCP settings see Scada Interface instruction manual included with the unit.3.4.1.5.3 Units with NODBUS RTU (Option 21S)Setting -> Default setting (Selection)Modbus Type -> Serial OnlyModbus Address -> 1 (1 – 247)Modbus Baud Rate -> 9600 (1200, 2400, 4800, 9600, 19200, 38400)Modbus Parity Type -> None (None, ADD, EVEN)Read Only Mode -> No (No, Yes)