NISSEI CORPORATION E6581815F-5266.18.5 Output phase failure detection : Output phase failure detection selection FunctionThis parameter detects inverter output phase failure. If the phase failure status persists for onesecond or more, the tripping function and the FL relay will be activated. At the same time, a tripinformation will also be displayed.=: No tripping (FL relay deactivated).=: With the power on, the phase failure detection is enabled only at the start of the first operation.The inverter will trip if the Phase failure status persists for one second or more.=: The inverter checks for output phase failures each time it starts operation. The inverter will trip ifthe Phase failure status persists for one second or more.[Parameter setting]Title Function Adjustment range Default setting Output phase failure detectionselection0: Disabled1: At start-up (only one time afterpower on)2: At start-up (each time)0Note 1: The rotor may move when the inverter output phase failure detection, if set this detect parameter 1 or 2.Please note the rotor does not move when the inverter is started.