NISSEI CORPORATION E6581815I-499.2.3 Compliance with Peripheral devicesUse the UL listed fuses at connecting to power supply.Short circuit test is performed under the condition of the power supply short-circuit currents in below.These interrupting capacities and fuse rating currents depend on the applicable motor capacities. AIC, Fuse and Wire sizesMaximumvoltage(V)Inputwithstandrating (kA)(1)Outputinterruptrating (kA) (2)Branch circuitprotectionRating(A)Wire sizes ofpower circuit Earth CableInverter model VFNC3M-2001P 240 5 5 Class CCFerrazATDR 3 AWG 14 AWG 14VFNC3M-2002P 240 5 5 Class CCFerrazATDR 5 AWG 14 AWG 14VFNC3M-2004P 240 5 5 Class CCFerrazATDR 7 AWG 14 AWG 14VFNC3M-2007P 240 5 5 Ferraz HSJ 15 AWG 14 AWG 14VFNC3M-2015P 240 5 5 Ferraz HSJ 25 AWG 14 AWG 14VFNC3M-2022P 240 5 5 Ferraz HSJ 25 AWG 12 AWG 14Suitable for use on a circuit capable of delivering not more than___X___rms symmetrical kilo Amperes,___Y___Voltsmaximum, when protected by___Z1___with a maximum rating of___Z2___.(1) Input withstand rating is that for which the product has been designed thermally. Installation on a supply greater thanthis level will require additional inductance to satisfy this level.(2) Output interrupt rating relies on Integral solid state short circuit protection. This does not provide branch circuitprotection. Branch circuit protection must be provided in accordance with the National Electrical Code and anyadditional local codes. This is dependant on the type of installation.9.2.4 Motor thermal protectionSelects the electronic thermal protection characteristics that fit with the ratings and characteristics of the motor.(thr (Motor electronic-thermal protection level 1) is set corresponding to each IPM gear motors at defaultsetting. Please consult our company when it is changed this setting value because there is a risk that a motor isburned out. Refer to section 3.4)