31Various function data can be changed and set when the operation is stopped.Note that some functions can be changed during operation. (See page 32.)Setting functions when operation is stopped.[Setting example: Change the maximum frequency from 50Hz to 60Hz][Setting precautions]1. After the function is set, the inverter will not run unless the MODE button ispressed and the "operation preparation completed" state is returned to.2. If the function setting returns to the "operation preparation completed"state during data changing, while a start input signal is being appliedthrough external control, an "OP" error will be displayed, causing theinverter to remain inoperative.∗ Reset the fault indication using the instructions under "Resetting FaultTrips" on page 73.3. The set data will be stored in the memory even after the power supply hasbeen turned OFF.Setting and Changing Functions(Changing the parameter P03 data from "50" to "60")Press the STOP button to stop the inverter.Press the SET button to display the parameter P03 data.(The main display will flicker.)STOPPress the (up) button twice, and change the parameter No. to P03.Press the MODE button.Press the MODE button.Press the MODE button. (Enter the function setting mode.)(If a password is set, it must be entered at this point. See page 62.)Press the (up) button, and change the data display value to "60".(The main display will flicker.)Press the SET button to set the data.Press the MODE button to return to "operation preparation completed."OPERATION PREPARATIONCOMPLETEDThe normal stop state will be entered and theinverter can be run.rd0605P 30P 10rF0 000 00P 40MODEMODEMODESETSETMODE