40LOCAL/EXTERNAL CONTROL (Parameter P08)Used to select whether to carry out start/stop and forward/reverse with the operation panel(local) or with signals input from external devices.DatasettingvalueLocal/ExternalPanelresetfunctionOperation method and control terminal connection diagram0 Start: RUN Stop: STOPForward/reverse: Set in dr mode1Local ProvidedForward run: , RUN Reverse run: , RUN Stop: STOP2 Notprovided4ExternalProvided356Common terminalON: Start/OFF: StopON: Reverse/OFF: Forward3 Notprovided5ExternalProvided356Common terminalON: Forward run/OFF: StopON: Reverse run/OFF: Stop∗∗∗∗ Panel reset functionWhen a fault trip occurs, the state cannot be reset with the external stop signal. Instead use"function to reset with the stop SW signal on the operation panel". Note that if the reset lockout function is used, that function will have the priority. The reset function is also valid.LOCAL/EXTERNAL FREQUENCY (Parameter P09)Used to select whether the frequency signal is to be set from the operation panel (local) orwith an input signal (external).DatasettingvalueLocal/ExternalFrequency settingsignal detailsOperation method and control terminalconnection diagram0 Potentiometer (panel)Frequency setting dialMax. : maximum frequency (Refer to P03, 15)Min. :Minimum frequency (or 0V stop)1LocalDigital setting (panel) Set with the "Fr mode" using the MODE, , andSET buttons.2 Potentiometer Terminals No. 1, 2, 3 (connect potentiometer'scenter tap to 2)3 0–5(V) voltage signal Terminals No.2 and 3 (2:+,3:–)4 0–10(V) voltage signal Terminals No.2 and 3 (2:+,3:–)5External4–20(mA) current signal Terminals No. 2 and 3, (2:+,3:–)Connect 200Ω across 2-3Note 1) When using the 4 to 20mA signal, always connect a "200Ω resistor" acrossterminals No. 2 and 3. (The inverter could be damaged if the 200Ω resistor is notconnected.)Note 2) When using an analog signal set to a value other than "1", the inverter will startand stop at a boundary of approx. 1/100 of the input signal's full scale. (0V stopfunction: refer to page 73.)