37Output voltage (%)Output frequencyOutput voltage (%)Output frequencyOutput voltage (%)Output frequency (Hz)100050 (Hz)100060 (Hz)Base frequency (P16)0100Max. output frequency(P15)1st ACCELERATION TIME (Parameter P01)Used to set the time to accelerate to the maximum outputfrequency from 0.5Hz.Data setting range (sec) 0.04 • 0.1 to 999Setting unit (sec) 0.1 (0.1 to 100) 1 (100 to 999)The display code for 0.04 sec. is "000".The maximum output frequency is set with parameters P03and P15.1st DECELERATION TIME (Parameter P02)Used to set the time to decelerate from the maximum outputfrequency to 0.5Hz.Data setting range (sec) 0.04 • 0.1 to 999Setting unit (sec) 0.1 (0.1 to 100) 1 (100 to 999)The display code for 0.04 sec. is "000".The maximum output frequency is set with parameters P03and P15.FREQUENCY RANGE (V/F PATTERN) (Parameter P03)A frequency range of 50/60Hz or 50 to 250Hz can be set independently from the maximumoutput frequency (50 to 250Hz).Data settingvalue Name Remarks50 50Hz mode60 60Hz modeThe frequency range is set regardless of the parameter P15 andP16 settings.FF Free modeThe frequency range is set according to the parameter P15 and P16settings.The maximum output frequency is set in parameter P15 and thebase frequency is set in parameter P16.[50Hz mode] [60Hz mode] [Free mode]· Max. output frequency · Max. output frequency= 50Hz = 60Hz· Base frequency = 50Hz · Base frequency = 60HzFunctional Descriptions (By Parameter )Output frequency(Hz)Max. outputfrequencyDecelera-tion time0.5Output frequency(Hz)Max. outputfrequencyAccelera-tion time0.5