66 Parameterizing WAGO-SPEEDWAY 767767-5203 Serial Interface (RS-232, RS-422/-485)ManualVersion 1.1.0Pos : 31.18 /Serie 767 ( WAGO-SPEED WAY)/Parametrier en/I/O-Module/Parametrier ung 767- xxxx Gl obal e Parameter @ 7\mod_1265881925390_21.doc x @ 50320 @ 2 @ 17.5 Global SettingsTable 38: Overview of parameters for the entire moduleParameter DescriptionSimulation diagnostic If the checkbox is selected, you can simulate a low voltage diagnostic.To generate a low voltage diagnostic, one or both of the two checkboxes"Low voltage U LS" and "Low voltage U A" must be selected.Default setting: unselectedLow voltage U LSIn the case of an undervoltage of the logic and sensor supply (U LS) orthe actuator supply (U A), the corresponding diagnostic is displayed here.Low voltage U APos : 31.19 /Serie 767 ( WAGO-SPEED WAY)/Parametrier en/I/O-Module/Parametrier ung 767-38xx, 5xxx, 6401, 7401 Param. der F el dvers orgung @ 5\mod_1249379780656_21.doc x @ 40285 @ 2 @ 17.6 Parameters of Field SupplyTable 39: Overview of adjustable parameters for the field supplyParameter DescriptionEnable field supply Switch on the field supply (24VDC) here.Default setting: selectedAutorestart delay In the event of a short circuit, the sensor supply is switched off for acertain time. Here, enter this delay time (in 100 ms increments) afterwhich the sensor supply is restarted.If the short circuit still exists, the process is repeated.Simulation diagnostic The simulation can be used to simulate a short circuit.Default setting: unselectedShort circuit/overload If simulation is deactivated, the respective error is displayed uponemergence.If simulation is activated, you can simulate one of the errors by selectingthe appropriate parameter.Pos : 31.20 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1