WAGO-I/O-SYSTEM 750 Configuration and Parameterization 53750-657 IO-Link MasterManualVersion 1.0.2, valid from FW/HW-Version 02/019.1.1.2.3.2 Diagnoses/ErrorsFigure 23: Display of diagnostic and error messagesTable 22: Display of diagnostic and error messagesOption DescriptionTimestamp Message timestampType Message type: “Error”, “Warning” or “Message”Channel Master, Port 1, Port 2, Port 3, Port 4Mode Unconfirmed message “Single shot“, “Appear“, “Disappear“Source Master/Appl. or DeviceInstance Event instance:0: Unknown1: Physical layer2: Data link layer3: Application layer4: ApplicationEvent Code Event code hexadecimal (see table "Event Codes of the IO-Link Masters")Description Description of the diagnostic message or eventIOLM-Error IOL master error code (see section "Error Messages")IOLD-Error IOL device error code (see section "Error Messages")FI-Index Specification of the record to be accessed (see section "FI_Index")Port Master, Port 1, Port 2, Port 3, Port 4Diagnostic and error messages are also displayed at the bottom of the window onthe configuration pages.Pos: 78.4 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1