1 Shield bus carrier2 Shield bus (10mm x 3mm)3 Shield clamp4 Cable shieldTo attach the shield the mounting of shield bus carriers are necessary. The shield buscarrier (available as accessory) serves to carry the shield bus to connect cable shields.1. Each System SLIO module has a carrier hole for the shield bus carrier. Push theshield bus carrier, until they engage into the module. With a flat mounting rail foradaptation to a flat mounting rail you may remove the spacer of the shield bus car-rier.2. Put your shield bus into the shield bus carrier.3. Attach the cables with the accordingly stripped cable screen and fix it by the shieldclamp with the shield bus.2.5.2 Wiring periphery modulesCAUTION!Do not connect hazardous voltages!If this is not explicitly stated in the corresponding module description,hazardous voltages are not allowed to be connected to the correspondingterminal module!With wiring the terminal modules, terminals with spring clamp technology are used forwiring. The spring clamp technology allows quick and easy connection of your signal andsupply lines. In contrast to screw terminal connections this type of connection is vibrationproof.Shield attachmentTerminal module terminalsVIPA System SLIOBasics and mountingWiring > Wiring periphery modulesHB300 | IM | 053-1EC01 | en | 18-4920