4.4.7 Accessing diagnostics dataHardware and diagnostic interrupt data of System SLIO modules with interrupt capabilitywere automatically sent by an emergency telegram if the interrupt is activated by parame-terization. There is also the possibility to request diagnostics data via SDO.The Alarm Status contains in each case a counter for hardware and diagnostic interruptsfor interrupt signaling. These counter are input data of the EtherCAT coupler and weretransferred together with the process data.DiagnosticIndex:Sub Name Type Offset Access Default Description0xF100:00 Diagnostic U8 0 ro 30xF100:01 Hardware inter-rupt counterU32 16 ro 0x00000000 Counter for hardware interrupt0xF100:02 Diagnostic inter-rupt counterU32 48 ro 0x00000000 Counter for diagnostic interrupt0xF100:03 DiagnosticModule StatusU64 80 ro 0x00000000 64 bit array, each bit represents a pending (butacknowledged) diagnostic alarmÄ ‘Explanation of the elements’ page 71n With de-activated Auto-Acknowledge of the EtherCAT coupler the correspondingcounter is set to 1 until you acknowledge this accordingly. For this you have to writeany value you like to subindex 0x06 under the accordingly assigned index.n With activated Auto-Acknowledge here you will find the number of hardware and diag-nostics interrupts, which happened since the last interrupt reset. To reset the corre-sponding counter you have to write any value you like to the subindex 0x06 under theaccordingly assigned index.There are the following index assignments:n Write to 0x06 of index 0x5000:– Reset of counter hardware interruptn Write to 0x06 of index 0x5002:– Reset of counter diagnostic interruptAlarm StatusVIPA System SLIO DeploymentAccessing the System SLIO > Accessing diagnostics dataHB300 | IM | 053-1EC01 | en | 18-49 63