A.4 Drive Derating DataThe drive can be operated at above the rated temperature, altitude, and default carrier frequency by derating the drive capacity.u Rated Current Depending on Carrier FrequencyThe tables below show the drive output current depending on the carrier frequency settings.The 2 kHz values shown in Table A.5 are equal to the drive rated current shown on the drive nameplate. Increasing the carrierfrequency above 2 kHz will reduce the rated output current of the drive.Table A.5 Three-Phase 600 V Class Carrier Frequency and Current DeratingThree-Phase 600 V ClassDrive Model Rated Current [A]2 kHz 8 kHz 10 kHz 15 kHz5A0003 2.7 2.2 2.0 1.35A0004 3.9 3.4 3.1 2.15A0006 6.1 4.9 4.3 2.95A0009 9 7.5 6.6 4.55A0011 11 9.3 8.2 5.65A0017 17 13.3 11.8 –5A0022 22 17.0 15.1 –5A0027 27 22.0 19.5 –5A0032 32 27.3 24.4 –Three-Phase 600 V ClassDrive Model Rated Current [A]2 kHz 5 kHz 8 kHz 10 kHz5A0041 41.0 39.7 33.5 29.45A0052 52.0 50.3 42.5 37.35A0062 62.0 61.3 49.7 41.95A0077 77.0 76.2 61.7 52.05A0099 99.0 80.0 55.1 –Three-Phase 600 V ClassDrive Model Rated Current [A]2 kHz 3 kHz5A0125 125.0 93.05A0145 145.0 108.05A0192 192.0 148.05A0242 242.0 187.0A.4 Drive Derating Data264 YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual