B.13 U: MonitorsMonitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.u U1: Operation Status MonitorsNo.(Addr.Hex) Name LCD Display Description AnalogOutput Level UnitU1-01(40) Frequency Reference Frequency Ref Monitors the frequency reference. Display units are determinedby o1-03. 10 V: Maxfrequency 0.01 HzU1-02(41) Output Frequency Output Freq Displays the output frequency. Display units are determined byo1-03. 10 V: Maxfrequency 0.01 HzU1-03(42) Output Current Output Current Displays the output current. 10 V: Driverated current <1> <2>U1-04(43) Control Method Control Method 0: V/f Control No signal outputavailable –U1-06(45) Output VoltageReference Output Voltage Displays the output voltage. 10 V: 575 Vrms 0.1 VacU1-07(46) DC Bus Voltage DC Bus Voltage Displays the DC bus voltage. 10 V: 1150 V 1 VdcU1-08(47) Output Power Output kWatts Displays the output power (this value is calculated internally). 10 V: Driverated power(kW)<1>U1-10(49) Input Terminal Status Input Term StsDisplays the input terminal status.U1 - 10=00000000 Digital input 1(terminal S1 enabled)Digital input 2(terminal S2 enabled)Digital input 3(terminal S3 enabled)Digital input 4(terminal S4 enabled)Digital input 5(terminal S5 enabled)Digital input 6(terminal S6 enabled)Digital input 7(terminal S7 enabled)1111111No signal outputavailable –U1-11(4A) Output Terminal Status Output Term StsDisplays the output terminal status.U1 - 11=00000000 Multi-FunctionDigital Output(terminal MD-ME-MF)Digital Output(terminal M1-M2)Digital Output(terminal M3-M4)Multi-FunctionMulti-FunctionNot UsedFault Relay(terminal MA-MC closedMA/MB-MC open)11110No signal outputavailable –B.13 U: MonitorsYASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual 317B Parameter List