9.2.4 Additionally for 2.03 (controller output 2 with function |6A|)The 0 - 10 V output signal A1 can, e.g., be used for triggering a shutter or heating.Setting Offset AnalogOutThe target value for this output is the target value (Setpoint) for the ventilation “offset”setting.Adjustment: range +/- 10,0 K relative to the active Setpoint.Example for triggering a shutter servomotor:At factory setting “0,0 K” = synchronous operation.The analog output is factory set to increasing activation during increasing temperature.Reprogramming to “Heating function”, i.e., increasing modulation during decreasingtemperature is possible ( IO Setup).0.0 KOffset AnalogOutSetting Pband AnalogOutPband AnalogOut = separately adjustable range of control (P-band) for 0 - 10 V outputSetting range: 0...200.0 KFactory setting: 2.0 K2.0 KPband AnalogOutSetting Min. AnalogOutMin. AnalogOut = Minimal output voltageSetting range: 0...100 % = 0 - 10 VFactory setting: 0 %0 %Min. AnalogOutSetting Max. AnalogOutMax. AnalogOut = Maximal output voltageSetting range: 100...0 % = 10 - 0 VFactory setting: 100 %100 %Max. AnalogOutExample for signal out 0 - 10 V (IO Setup: “A2 function” = |6A|)Max. Analog Out10 V50 %100 %IMin. Analog OutMin. 0 % Max. = 100 %Min. 35 % Max. = 85 %20 °CS 10 KR30 °C 09.05.2007v_signal_ausgang_0_10_v.vsdExample: Setpoint ventilation 25.0°C, Offset -5.0 K, Pband 10.0 KS Setpoint Ventilation +/- OffsetR PbandI Actual valueOperating Instructions Fcontrol – model series FXDM25/32AM ProgrammingL-BAL-E212-GB 1451 Index 003 Part.-No.38/123