6.01 Air velocity control, Setpoint in m/sMain menu SettingStartSettingProtocolBase setupController SetupBase setup Setpoint1Setting range: in measuring range of sensorFactory setting: 0.50 m/s0.50 m/sSetpoint1Base setup Setpoint2Setting “Setpoint 2” e.g. reduced value for night operation.Switch over Setpoint 1/2 by external contact (display as long as no allocation is carriedout: | - - - - -| IO Setup).- - - - -Setpoint2Base setup PbandNarrow control range = Short control timesWide control range = Longer control times and more stable controlSetting range: in measuring range of sensorFactory setting: 0.50 m/s0.50 m/sPbandSetting Min. Speed (basic speed only when needed)Setting range: |OFF| → “Shutdown Freq.” ( Motor Setup) - “Max. Speed”.Factory setting: |OFF |OFFMin. SpeedSetting Max. Speed (speed limitation only when needed)Setting range: “Max. Frequency” ( Motor Setup) - “Min. Speed”Factory setting: 50.0 Hz50.0 HzMax. SpeedSetting Manual mode“OFF” = automatic control as function of the set parameters (Factory setting)“ON” = automatic control without function, speed setting in menu “Speed manual”OFFManual modeSetting Speed Manual modeManual speed setting without influence by the external signal.Activation by menu “Manual mode” or external contact at digital input ( IO Setup).Setting range: 0... “Max. Frequency” ( Motor Setup)Factory setting: 50.0 HzFor information about deactivated regulation the adjusted value for manual speed isindicated alternating with the actual value.50.0 HzSpeed man.Operating Instructions Fcontrol – model series FXDM25/32AM ProgrammingL-BAL-E212-GB 1451 Index 003 Part.-No.52/123