9.12 Motor SetupMain menu Motor SetupController SetupIO SetupLimitsMotor SetupDiagnostic9.12.1 Setting motor rated currentMotor Setup MotorRatedCurr.Possible setting for the motor rated current.The setting for the “DC brake level” ( setting brake behaviour) refers to this setting.Setting range: 0.0...device rated current / AFactory setting: device rated current32 AMotorRatedCurr.9.12.2 Setting motor rated voltageMotor Setup MotorRatedVolt.When commissioning, you must set the motor to the rated voltage stated on therating plate.An adaptation can be made if the motor rated-voltage as the applied mains voltage islower (e.g. 3 ~ 230 V motor on 3 ~ 400 V mains).Verify the output voltage using suitable measuring instruments.Setting range: 0...500 VFactory setting: 400 V400 VMotorRatedVolt.9.12.3 Adjustment of the U/f curveInformationThe device comes supplied with a preprogrammed square characteristic curve for the oper-ation of fans.In the case of voltage-controllable motors and square load torque-moments (e.g. fans andpump operation), an optimal speed control is generally achieved through this.In systems in which high dynamics are required, switchover to a linear characteristic musttake place. Generally speaking, if the load characteristic is not known as a definite value, thelinear characteristic should be set. In the case of linear characteristic curves, the motorachieves full torque throughout the entire speed range. For this, a thermal overload of themotor must be prevented through suitable measures (complete motor protection throughusing thermocontact or PTC thermistor-monitoring).Motor Setup EdgefrequencyThe maximum output voltage is attained during break edge frequency.Adjustment range: 10.0 - 150.0 HzFactory setting: 48.5 HzIn the case of special settings with “Edge frequency” > “Maximum frequency”, due tohigher power losses it is possible that automatic power reduction, “derating”, occurs.48.5 HzEdgefrequencyMotor Setup Max. FrequencyAbove the Edgefrequency, the frequency is merely increased up to the Maximumfrequency.Adjustment range: 10.0 - 150 HzFactory setting: 50.0 Hz50.0 HzMax. FrequencyOperating Instructions Fcontrol – model series FXDM25/32AM ProgrammingL-BAL-E212-GB 1451 Index 003 Part.-No.89/123