9.5.9 Group control9.5.9.1 Group versionGroups can be controlled by the analogue output “A” or the relay outputs “K1” and “K2”.Controller Setup Following group versions are available:0: One controlled group and up to three switched groups (factory setting)1: Two controlled groups0Group versionInformation• The groups must be connected at the appropriate programmed output when activating by theanalogue outputs and relays.• The assignment of the analogue outputs and the relays for the group control takes place in the IOSetup.• The number of possible groups depends on the available hardware outputs.9.5.9.2 Group variant 0: One controlled group and up to three switched groupsControl group 2/3/4 via relaisController Setup Group 2 ON valueSwitch-on value for Group2Setting range: 0 - 100 %Factory setting: 50 % *50 %Group 2 ON valueController Setup OFF Value Group2Switch-off value for group2Setting range: 0 - 100 %Factory setting: 45 % *45 %OFF Value Group2Controller Setup nmin at Group2Minimum Value for Group2Setting range: 0 - 100 %Factory setting: 20 % *20 %nmin at Group2Controller Setup Group 3 ON valueSwitch-on value for Group3Setting range: 0 - 100 %Factory setting: 70 % *70 %Group 3 ON valueController Setup OFF Value Group3Switch-off value for group3Setting range: 0 - 100 %Factory setting: 65 *65 %OFF Value Group3Controller Setup nmin at Group3Minimum Value for Group3Setting range: 0 - 100 %Factory setting: 30 % *30 %nmin at Group3Operating Instructions Fcontrol – model series FKDM25/32AM-C ProgrammingL-BAL-E214-GB 1446 Index 002 Part.-No.42/99