9.8 Motor SetupMain menu Motor SetupController SetupIO SetupLimitsMotor SetupDiagnostic9.8.1 Setting motor rated currentMotor Setup MotorRatedCurr.Possible setting for the motor rated current.The setting for the “DC brake level” ( setting brake behaviour) refers to this setting.Setting range: 0.0...device rated current / AFactory setting: device rated current32 AMotorRatedCurr.9.8.2 Setting motor rated voltageMotor Setup MotorRatedVolt.When commissioning, you must set the motor to the rated voltage stated on therating plate.An adaptation can be made if the motor rated-voltage as the applied mains voltage islower (e.g. 3 ~ 230 V motor on 3 ~ 400 V mains).Verify the output voltage using suitable measuring instruments.Setting range: 0...500 VFactory setting: 400 V400 VMotorRatedVolt.9.8.3 Adjustment of the U/f curveInformationSettings for U/f characteristic may only be made when no motor modulation is present!Motor Setup EdgefrequencyThe maximum output voltage is attained during break edge frequency.Adjustment range: 10.0 - 150.0 HzFactory setting:1.10 , 3.10 , 3.20 = 48.5 Hz1.11 , 3.11 , 3.21 = 85.0 Hz48.5 HzEdgefrequencyMotor Setup Max. FrequencyAbove the Edgefrequency, the frequency is merely increased up to the Maximumfrequency.Adjustment range: 10.0 - 150 HzFactory setting:1.10 , 3.10 , 3.20 = 50.0 Hz1.11 , 3.11 , 3.21 = 87.0 Hz50.0 HzMax. FrequencyMotor Setup Shutdown Freq.Below the Shutdown Freq. the output is switched off (hysteresis approx. 1.5 % setting“Max. Frequency”) .Adjustment range: 5.0 - 150 HzFactory setting: 5.0 Hz5.0 HzShutdown Freq.Operating Instructions Fcontrol – model series FKDM25/32AM-C ProgrammingL-BAL-E214-GB 1446 Index 002 Part.-No.68/99