121411 222421K1 K2 11.05.2007v_relais_k1_k2.vsdK1 1 = energized, terminals 11-14 bridged0 = de-energized, terminals 11-12 bridgedK2 1 = energized, terminals 21-24 bridged0 = de-energized, terminals 21-22 bridgedFunction Controller status K1/ K21 = energized0 = de-energizedInvertingOFF ON1K Operation without fault, line supply okay 1 02K Fault with indication by relay 0 13K Ext. Fault at digital input for external fault 1 04K Over or falling below limits for modulation 1 05K over or falling below limits for input signal “E1” 1 06K over or falling below limits for input signal “E2” 1 07K setpoint deviation to high 1 08K Activation of second group 1 012K Activation of third group 1 013K Activation of fourth group 1 09.6.5 Programming Add-on module type Z-Modul-BAfter connecting the module, the menu group “IO Setup” is followed automatically by the additionmalmenu group “IO Extension” in which the settings for the inputs and outputs of the module are made.• 1 x analog input 0 - 10 V. For mode 1.01 without function, starting from 2.01 funktion |1E| or |2E|possible.– Function |1E| for external target value function.– Function |2E| for external manual operation.• 1 x output 0 - 10 V (A2 / GND), Function programmable, e.g., for: Fixed voltage, proportional levelcontrol, proportional input signal, group control, drive 2.• 3 x digital inputs (D3 / GND, D4 / GND, D5 / GND) function programmable, e.g.: Enable (ON /OFF), external malfunction, output limitation, input 1/2, target value 1/2, internal/external preset,controller / manual operation, control-function reversal (“heating” / “cooling”).• 2 x relay outputs (“K3” and “4K”) Function programmable, e.g., for: Status signals, alarm indications,external malfunctions at the digital input, level-control threshold, input signal threshold, offsetthreshold (deviation between current and target value), group control.Operating Instructions Fcontrol – model series FKDM25/32AM-C ProgrammingL-BAL-E214-GB 1446 Index 002 Part.-No.62/99