9.6 IO SetupMain menu IO SetupProtocolBase setupController SetupIO SetupLimits9.6.1 Analog-Output “A”IO Setup The analog outputs 0 - 10 V can be allocated with various functions.Terminals “A” - “GND” = AnalogOut (Imax Technical data)Constant voltage 10 V(1A)A FunctionIO Setup With the attitudes “A min” and “A max” the characteristic of the output voltage can beadapted.Setting range: “A min.” = 0 - 5 V, “A max.” = 10 - 5 VFactory setting: “A min.” = 0 V, “A max.” = 10 V0.0 VA min.IO Setup10.0 VA max.IO Setup With the attitudes “A Inverting” the output voltage can inverted.Factory setting: “A Inverting” = “OFF”OFFA InvertingFunction DescriptionOFF No functionConstant voltage 10 V(1A)Constant voltage +10 V (factory setting)1st control signal(2A)Proportional to the internal activation of the power unit (control circuit 1) under consid-eration of “Min. Speedl” and “Max. Speed”.• for enable “OFF” it goes back to 0 V• for motor fault the output signal remains for a slave controller (“Master-Slave”combination).E1(3A)proportional input “E1 ”E2(4A)proportional input “E2 ”Group2(5A)Group control ( Controller Setup - group 2)2.Cooling(6A)Only in mode 2.03 temperature controller with additional functions (not for Z-Module-B).Controller output 2 with rising activation at Actual>Nominal = Cool.2.Heating(7A)Only in mode 2.03 temperature controller with additional functions (not for Z-Module-B).Controller output 2 with rising activation at Actual Heat.Operating Instructions Fcontrol – model series FKDM25/32AM-C ProgrammingL-BAL-E214-GB 1446 Index 002 Part.-No.46/99