9.6.2.6 Set 1/2 or Setpoint 1/2, Function |5D|Switch over between “Set Intern1” and “Set Intern2” (for speed controller 1.10 ... 1.11 ).Contact at digital input e.g. “Digital In 1”.ControllerD1 D110n = 40 %1n = 80 %0- - - - -- - - - -27.11.2008v_5d_vorgabe_intern_1_2_m.vsd12 M• “D1 Inverting” = “OFF”: “Set Intern1” atopened contact / “Set Intern2” at closedcontact.• “D1 Inverting” = “ON”: “Set Intern1” atclosed contact / “Set Intern2” at openedcontact.Info Operation with “Set Intern2” is signalized by the moon symbol for reduced operation.“Set extern1” under “settings” must be programmed to “OFF”.50 %ModulationSwitch over between “Setpoint1” and “Setpoint2” (for modes as controller higher 3.10 )For operation with second control circuit: switch over “1.Setpoint 1” / “1.Setpoint 2”Contact at digital input e.g. “Digital In 1”.Controller10n = 0 – 100 %- - - - -- - - - -Sensor27.11.2008v_5d_sollwert_1_2_m.vsd12D1 D1M1 Setting “Setpoint 1” or “1.Setpoint 1” (display in operation with twocontrol circuits for Setpoint 1 of control circuit 1)2 Setting “Setpoint 2” or “1.Setpoint 2” (display in operation with twocontrol circuits for Setpoint 2 of control circuit 1)• “D1 Inverting” = “OFF”: “Setpoint1” = 18 °Cat opened contact / “Setpoint2” = 25 °C atclosed contact.• “D1 Inverting” = “ON”: “Setpoint1” = 18 °Cat closed contact / “Setpoint2” = 25 °C atopened contact.Info Operation with “Setpoint2” is signalized by the moon symbol for reduced operation.28.7 °CE1 Actual9.6.2.7 Intern / Extern Function |6D|Switch over between Set Intern and Set Extern (for mode speed controller 1.10 ... 1.11 ). “Setextern1” under settings must be programmed to “OFF”.Contact at digital input e.g. “Digital In 1”.ControllerD1 D110n = 40 %n = 80 %Si 40 %- - - - -E127.11.2008v_6d_vorgabe_intern_extern_m.vsd10 MSi Signal1 Setting “Set Intern1” (depending on device type in: %, Hz, rpm)• “D1 Inverting” = “OFF”: “Set Intern1” atopened contact / “Setting Extern” at closedcontact.• “D1 Inverting” = “ON”: “Set Intern1” atclosed contact / “Set Extern” at openedcontact.Operating Instructions Fcontrol – model series FKDM25/32AM-C ProgrammingL-BAL-E214-GB 1446 Index 002 Part.-No.51/99