11 Diagnostics menuMain menu The diagnostics menu supplies information about the momentary operating conditionof the device.IO SetupLimitsTimerAutoaddressingDiagnostic000419:27:28Runtime ControllerOperating hours on the lineThe time counter (h:m:s) runs as soon as line voltage is applied to the device and thedevice is switched on (without failure).If events step on (Motor fault, External Error, etc.), the period of operation is stored atthis time ( Protocol).000146:23:54Runtime MotorOperating hours with modulationThe time counting (h:m:s) runs only when a modulation of the controller is present585 VDC-VoltageDC-VoltageThe intermediate circuit voltage without load is the peak value of the input voltage.In a three-phase supply network with 400 V, an intermediate circuit voltage of ca. 565 Vresults. This voltage sinks slightly under load.400 VLine voltageLine voltage28.1 °CIGBT temperatureIGBT temperatureDisplay of the internal temperature of the power semiconductor. During impermissiblyhigh levels (at 90 °C), the output power is automatically reduced. At 105 °C switch off.29.5 °CFilterchokeFilterchoke30.1 °CSinefilterSinefilterDisplay of sine filter choke temperature. In case of temperature increase above prede-termined threshold value the modulation is switched off. Restart when cooled down!(only in version with integrated sine filter)20.0 °CE1 - KTYE1Signal height at analog input E1 (Analog In 1)9.0 mAE1-Current4.0 VE1 - Voltage20.0 °CE2 - KTYE2Signal height at analog input E2 (Analog In 2)9.0 mAE2 - CurrentOperating Instructions Fcontrol – model series FKDM25/32AM-C Diagnostics menuL-BAL-E214-GB 1446 Index 002 Part.-No.88/99