Diagnostics RTU500 series Remote Terminal UnitHardware Tree3-4 | 1KGT 150 924 V000 1 - ABB AGThe Hardware tree page gives information about the configuration of the RTU and about the actualvalues of the process objects according the configuration in RTUtil500 (see "Fig. 34: Hardware treepages").The channel number, process object ID and the current value of the data point is shown in the rightwindow. The value and the status information is updated cyclically.Figure 34: Hardware tree pagesBy selecting a binary or analoge output module, it is possible to perform commands directly to theconnected primary process (see "Fig. 34: Hardware tree pages").A D V I C EThe output control function is only for test purposes during commissioning phase. It is not allowedto use this function to send commands to an active process.In order to perform commands out of the Web server, the following pre-conditions must be fulfilled:• The debugging option must be generally enabled (see chapter Chapter 2.5.1)• The user must have the privileges to perform commands (see chapter Chapter 2.5.3)• The debugging option must be temporary enabled (see chapter Chapter )3.3.2 Board DiagnosisSelect a communication unit in the hardware tree to get information about it's state.