CL-8- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE19XRV PIC III SETUP1 TABLE CONFIGURATION SHEETNOTE: No variables are available for CCN read operation. Forcing shall not be supported on service screens.DESCRIPTION RANGE UNITS POINT DEFAULT VALUEComp Motor Temp Override 150 to 200(66 to 93)DEG F(DEG C) MT_OVER 200(93)Cond Press Override 90 to 165(621 to 1138)PSI(kPa) CP_OVER 125(862)Rectifier Temp Override 155 to 170(68 to 77)DEG F(DEG C) REC_OVER 160(71)Inverter Temp Override 155 to 170(68 to 77)DEG F(DEG C) INV _OVER 160(71)Comp Discharge Alert 125 to 200(52 to 93)DEG F(DEG C) CD_ALERT 200(93)Comp Thrust Brg Alert 165 to 185(74 to 85)DEG F(DEG C) TB_ALERT 175(79)Comp Thrust Brg Trip 160 to 185(71 to 85)DEG F(DEG C) TB_TRIP 185(85)Thrust Brg Reset Factor 1.0 to 3.0 TB_POWER 1.4Chilled Medium 0/1 WATER/BRINE MEDIUM WATERChilled Water Deadband .5 to 2.0(0.3 to 1.1)ˆF(ˆC) CWDB 1.0(0.6)Evap Refrig Trippoint 0.0 to 40.0(–17.8 to 4.4)DEG F(DEG C) ERT_TRIP 33.0(0.6)Refrig Override Delta T 2.0 to 5.0(1.1 to 2.8)ˆF(ˆC) REF_OVER 3.0(1.7)Evap Approach Alert 0.5 to 30.0(0.3 to 16.7)ˆF(ˆC) EVAP_AL 5.0(2.8)Cond Approach Alert 0.5 to 30.0(0.3 to 16.7)ˆF(ˆC) COND_AL 6.0(3.3)Condenser Freeze Point –20 to 35(–28.9 to 1.7)DEG F(DEG C) CDFREEZE 34(1.1)Flow Delta P Display 0/1 DSABLE/ENABLE FLOWDISP DSABLEEvap Flow Delta P Cutout 0.5 to 50.0(3.4 to 344.8)PSI(kPa) EVAP_CUT 5.0(34.5)Cond Flow Delta P Cutout 0.5 to 50.0(3.4 to 344.8)PSI(kPa) COND_CUT 5.0(34.5)Cond Hi Flow Del P Limit 0.5 to 50.0(3.4 to 344.8)PSI(kPa) COND_ALM 50.0(344.8)Cond Hi Flow Alarm Opt 0/1 DSABLE/ENABLE COND_VAL DSABLEWater Flow Verify Time 0.5 to 5 MIN WFLOW_T 5Oil Press Verify Time 15 to 300 SEC OILPR_T 40Recycle ControlRestart Delta T 2.0 to 10.0(1.1 to 5.6)DEG F(DEG C) rcycr_dt 5.0(2.8)Shutdown Delta T 0.5 to 4.0(0.3 to 2.2)DEG F(DEG C) rcycs_dt 1.0(.0.6)Spare Alert/Alarm EnableDisable=0, Lo=1/3, Hi=2/4Spare Temp #1 Enable 0 to 4 sp1_en 0Spare Temp #1 Limit –40 to 245(–40 to 118)DEG F(DEG C) sp1_lim 245(118)Spare Temp #2 Enable 0 to 4 sp2_en 0Spare Temp #2 Limit –40 to 245(–40 to 118)DEG F(DEG C) sp2_lim 245(118)