99Table 16 — Alarm and Alert Messages (cont)H. OUT-OF-RANGE SENSORICVC FAULTSTATEPRIMARYMESSAGESECONDARYMESSAGE PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY260 SENSOR FAULTLEAVING CHILLEDWATER260Sensor Fault: CheckLeaving Chilled Water Sensor.Check sensor resistance or voltage drop.Check for proper wiring.Check for disconnected or shorted wiring.261 SENSOR FAULTENTERING CHILLEDWATER261Sensor Fault: CheckEntering Chilled WaterSensor.Check sensor resistance or voltage drop.Check for proper wiring.Check for disconnected or shorted wiring.262 SENSOR FAULTCONDENSER PRESSURE 262Sensor Fault: CheckCondenser Pressure Sensor.Check sensor wiring.Check for disconnected or shorted wiring.Check for condensation in transducerconnector.263 SENSOR FAULTEVAPORATORPRESSURE263Sensor Fault: CheckEvaporator Pressure Sensor.Check sensor wiring.Check for disconnected or shorted wiring.Check for condensation in transducerconnector.264 SENSOR FAULTCOMPRESSOR BEARINGTEMP264Sensor Fault: CheckComp Thrust Brg Temp Sen-sor.Check sensor resistance or voltage drop.Check for proper wiring.Check for disconnected or shorted wiring.265 SENSOR FAULTCOMPRESSOR MOTORTEMP265Sensor Fault: CheckComp Motor Winding TempSensor.Check sensor resistance or voltage drop.Check for proper wiring.Check for disconnected or shorted wiring.266 SENSOR FAULTCOMP DISCHARGE TEMP 266Sensor Fault: CheckComp Discharge Temp Sensor.Check sensor resistance or voltage drop.Check for proper wiring.Check for disconnected or shorted wiring.267 SENSOR FAULTOIL SUMP TEMP 267Sensor Fault: Check OilSump Temp Sensor.Check sensor resistance or voltage drop.Check for proper wiring.Check for disconnected or shorted wiring.268 SENSOR FAULTCOMP OIL PRESS DIFF 268Sensor Fault: Check OilPump Delta P Sensor.Check sensor resistance or voltage drop.Check for proper wiring.Check for disconnected or shorted wiring.269 SENSOR FAULTCHILLED WATER FLOW 269Sensor Fault: CheckChilled Water Delta P Sensor.Check sensor wiring and accuracy.Check for disconnected or shorted wiring.If pressure transducers are not installed,check for presence of resistors and jumperson lower CCM terminal block J3.270 SENSOR FAULTCOND WATER FLOW 270Sensor Fault: CheckCond Water Delta P Sensor.Check sensor wiring and accuracy.Check for disconnected or shorted wiring.If pressure transducers are not installed,check for presence of resistors and jumperson lower CCM terminal block J3.271 SENSOR FAULTEVAP SATURATION TEMP 271Sensor Fault: CheckEvap Saturation Temp Sensor.Check sensor resistance or voltage drop.Check for proper wiring.Check for disconnected or shorted wiring.