Parameters: Digital In/Out5-** Digital In/OutParameter group for configuring the digital inputand output.5-0* Digital I/O ModeParameters for configuring the IO mode. NPN/PNPand setting up IO to Input or Output.5-00 Digital I/O ModeValue:PNP [0]NPN [1]Function:Digital inputs and programmed digital outputs arepre-programmable for operation either in PNP orNPN systems.Select PNP [0] systems for action on positive di-rectional pulses (↕). PNP systems are pulled downto GND.Select NPN [1] systems for action on negative di-rectional pulses (↕). NPN systems are pulled up to+ 24 V, internally in the frequency converter.This parameter cannot be adjusted while the mo-tor is running.NB!When changing this parameter, a pow-er cycle must be carried out before theparameter change is active.5-01 Terminal 27 ModeValue:Input [0]Output [1]Function:Select Input [0] to define terminal 27 as a digitalinput.Select Output [1] to define terminal 27 as a digitaloutput.This parameter cannot be adjusted while the mo-tor is running.5-02 Terminal 29 ModeValue:Input [0]Output [1]Function:Select Input [0] to define terminal 29 as a digitalinput.Select Output [1] to define terminal 29 as a digitaloutput.This parameter is available for FC 302 only.This parameter cannot be adjusted while the mo-tor is running.5-1* Digital InputsParameters for configuring the input functions forthe input terminals.The digital inputs are used for selecting variousfunctions in the frequency converter. All digital in-puts can be set to the following functions:Digital input function Select TerminalNo operation [0] All *term 32, 33Reset [1] AllCoast inverse [2] All *term 27Coast and reset inverse [3] AllQuick stop inverse [4] AllDC-brake inverse [5] AllStop inverse [6] AllStart [8] All *term 18Latched start [9] AllReversing [10] All *term 19Start reversing [11] AllEnable start forward [12] AllEnable start reverse [13] AllJog [14] All *term 29Preset reference on [15] AllPreset ref bit 0 [16] AllPreset ref bit 1 [17] AllPreset ref bit 2 [18] AllFreeze reference [19] AllFreeze output [20] AllSpeed up [21] AllSpeed down [22] AllSet-up select bit 0 [23] AllSet-up select bit 1 [24] AllPrecise stop inverse [26] 18, 19Precises start, stop [27] 18, 19Catch up [28] AllSlow down [29] AllCounter input [30] 29, 33Pulse input [32] 29, 33Ramp bit 0 [34] AllRamp bit 1 [35] AllMains failure inverse [36] AllLatched precise start [40] 18, 19Latched precise stop in-verse[41] 18, 19DigiPot Increase [55] AllDigiPot Decrease [56] AllDigiPot Clear [57] AllCounter A (up) [60] 29, 33Counter A (down) [61] 29, 33Reset Counter A [62] AllCounter B (up) [63] 29, 33Counter B (down) [64] 29, 33Reset Counter B [65] AllAll = Terminals 18, 19, 27, 29, 32, 33, X30/2,X30/3, X30/4. X30/ are the terminals on MCB101.Terminal 29 is available in FC 302 only.FC 300 Design GuideHow to Programmefactory setting () display text [] value for use in communication via serial communication portMG.33.B7.02 - VLT is a registered Danfoss trademark 165