Parameters: EncoderInput17-** Motor Feedb. OptionAdditional parameters to configure the Encoder(MCB102) or the Resolver (MCB103) FeedbackOption.17-1* Inc. Enc. InterfaceParameters in this group configure the incremen-tal interface of the MCB102 option. Note that boththe incremental and absolute interfaces are activeat the same time.17-10 Signal TypeValue:None [0]RS422 (5V TTL/linedrv.) [1]Sinusoidal 1Vpp [2]Function:Select the incremental type (A/B channel) of theencoder in use. Find the information on the en-coder data sheet.Select None [0] if the feedback sensor is an ab-solute encoder only.This parameter cannot be adjusted while the mo-tor is running.17-11 Resolution (PPR)Value:10 - 10000 1024Function:Enter the resolution of the incremental track, i.e.the number of pulses or periods per revolution.This parameter cannot be adjusted while the mo-tor is running.17-2* Abs. Enc. InterfaceParameters in this group configure the absoluteinterface of the MCB102 option. Note that both theincremental and absolute interfaces are active atthe same time.17-20 Protocol SelectionValue:None [0]HIPERFACE [1]EnDat [2]SSI [4]Function:Select HIPERFACE [1] if the encoder is absoluteonly.Select None [0] if the feedback sensor is an in-cremental encoder only.This parameter cannot be adjusted while the mo-tor is running.17-21 Resolution (Positions/Rev)Value:512 [512]1024 [1024]2048 [2048]4096 [4096]SSI 4 - 8192 [8192]16384 [16384]HIPERFACE 512 - 32768 [32768]Function:Select the resolution of the absolute encoder, i.e.the number of counts per revolution.This parameter cannot be adjusted while the mo-tor is running.17-24 SSI Data LengthValue:13 - 25 13Function:Set the number of bits for the SSI telegram.Choose 13 bits for single-turn encoders and 25bits for multi-turn encoder.17-25 Clock RateValue:100 - 260 kHz 260kHzFunction:Set the SSI clock rate. By long encoder cables theclock rate must be reduced.17-26 SSI Data FormatValue:Gray Code [0]Binary Code [1]FC 300 Design GuideHow to Programmefactory setting () display text [] value for use in communication via serial communication port236 MG.33.B7.02 - VLT is a registered Danfoss trademark