Parameters: Drive Informa-tion15-** Operating DataParameter group containing frequency converterinformation such as operating data, hardwareconfiguration and software versions.15-0* Operating DataParameter group containing operating data e.g.Operating Hours, kWh counters, Power Ups, etc.15-00 Operating HoursValue:0 - 2147483647 h 0hFunction:View how many hours the frequency converterhas run. The value is saved when the frequencyconverter is turned off.15-01 Running HoursValue:0 - 2147483647 h 0hFunction:View how many hours the motor has run. Resetthe counter in par. 15-07. The value is savedwhen the frequency converter is turned off.15-02 kWh CounterValue:0 - 2147483647 kWh 0kWhFunction:View the power consumption from mains in kWhas a mean value over one hour. Reset the counterin par. 15-06.15-03 Power Up'sValue:0 - 2147483647 0Function:View the number of times the frequency converterhas been powered up.15-04 Over Temp'sValue:0 - 65535 0Function:View the number of frequency converter temper-ature faults which have occurred.15-05 Over Volt'sValue:0 - 65535 0Function:View the number of frequency converter overvol-tages which have occurred.15-06 Reset kWh CounterValue:*Do not reset [0]Reset counter [1]Function:Select Reset [1] and press [OK] to reset the kWhcounter to zero (see par 15-02). This parametercannot be selected via the serial port, RS 485.Select Do not reset [0] if no reset of the kWhcounter is desired.NB!The reset is carried out by pressing[OK].15-07 Reset Running Hours CounterValue:Do not reset [0]Reset counter [1]Function:Select Reset [1] and press [OK] to reset the Run-ning Hours counter to zero (see par. 15-01). Thisparameter cannot be selected via the serial port,RS 485.Select Do not reset [0] if no reset of the RunningHours counter is desired.15-1* Data Log SettingsThe Data Log enables continuous logging of up to4 data sources (par. 15-10) at individual rates(par. 15-11). A trigger event (par. 15-12) andwindow (par. 15-14) are used to start and stopthe logging conditionally.FC 300 Design GuideHow to Programmefactory setting () display text [] value for use in communication via serial communication portMG.33.B7.02 - VLT is a registered Danfoss trademark 223