EMC Test Results (Emission, Immunity)The following test results have been obtained using a SYSTEM with a frequency converter (with op-tions if relevant), a screened control cable, a control box with potentiometer, as well as a motor andmotor screened cable.Conducted emission Radiated emissionIndustrial environment Housing,trades andlight indus-triesIndustrial en-vironmentHousing, tradesand light indus-triesEN 55011Class A2EN 55011Class A1EN 55011Class BEN 55011Class A1EN 55011 Class BSetupFC 301/FC 302 (H2)0-3.7 kW 200-240 V0-7.5 kW 380-480/500 V5 m5 mNoNoNoNoNoNoNoNoFC 301 (H1)0-3.7 kW 200-240 V0-7.5 kW 380-480 V75 m75 m50 m50 m10 m10 mYesYesNoNoFC 301 (H3)0-1.5 kW 200-240 V0-1.5 kW 380-480 V50 m50 m25 m25 m2.5 m2.5 mYesYesNoNoFC 302 (H1)0-3.7 kW 200-240 V0-7.5 kW 380-500 V150 m150 m150 m150 m50 m50 mYesYesNoNoFC 301/FC 302 (H2)11-22 kW 380-480/500 V 25 m No No No NoFC 301 (H1)11-22 kW 380-480 V 75 m 50 m 10 m Yes NoFC 302 (H1)11-22 kW 380-500 V 150 m 150 m 50 m Yes NoFC 302 (HX)0.75 - 7.5 kW550 - 600 V No No No No NoHX, H1, H2 or H3 is defined in the type code pos. 16 - 17 for EMC filtersHX - No EMC filters build in the frequency converter (600 V units only)H1 - Integrated EMC filter. Fulfil Class A1/BH2 - No additional EMC filter. Fulfil Class A2H3 - Integrated EMC filter. Fulfil class A1/B (Enclosure type A1 only)FC 300 Design GuideIntroduction to FC 300MG.33.B7.02 - VLT is a registered Danfoss trademark 37