Parameters: Profibus9-** ProfibusParameter group for all Profibus-specific parame-ters.9-00 SetpointValue:0-65535 0Function:This parameter receives cyclical reference from aMaster Class 2. If the control priority is set to Mas-ter Class 2, the reference for the frequency con-verter is taken from this parameter, whereas thecyclical reference will be ignored.9-07 Actual ValueValue:0-65535 0Function:This parameter deliveres the MAV for a MasterClass 2. The parameter is valid if the control pri-ority is set to Master Class 2.9-15 PCD Write ConfigurationArray [10]Value:None3-02 Minimum Reference3-03 Maximum Reference3-12 Catch Up/Slow Down Value3-41 Ramp 1 Ramp Up Time3-42 Ramp 1 Ramp Down Time3-51 Ramp 2 Ramp Up Time3-52 Ramp 2 Ramp Down Time3-80 Jog Ramp Time3-81 Quick Stop Ramp Time4-11 Motor Speed Low Limit [RPM]4-13 Motor Speed High Limit [RPM]4-16 Torque Limit Motor Mode4-17 Torque Limit Generator Mode7-28 Minimum Feedback7-29 Maximum Feedback8-90 Bus Jog 1 Speed8-91 Bus Jog 2 Speed16-80 Fieldbus CTW 116-82 Fieldbus REF 134-01 PCD 1 Write to MCO34-02 PCD 2 Write to MCO34-03 PCD 3 Write to MCO34-04 PCD 4 Write to MCO34-05 PCD 5 Write to MCO34-06 PCD 6 Write to MCO34-07 PCD 7 Write to MCO34-08 PCD 8 Write to MCO34-09 PCD 9 Write to MCO34-10 PCD 10 Write to MCOFunction:Select the parameters to be assigned to PCD 3 to10 of the telegrams. The number of availablePCDs depends on the telegram type. The values inPCD 3 to 10 will then be written to the selectedparameters as data values. Alternatively, specifya standard Profibus telegram in par. 9-22.9-16 PCD Read ConfigurationArray [10]Value:None16-00 Control Word16-01 Reference [Unit]16-02 Reference %16-03 Status Word16-04 Main Actual Value [Unit]16-05 Main Actual Value [%]16-09 Custom Readout16-10 Power [kW]16-11 Power [hp]16-12 Motor Voltage16-13 Frequency16-14 Motor Current16-16 Torque16-17 Speed [RPM]16-18 Motor Thermal16-19 KTY Sensor Temperature16-21 Phase Angle16-30 DC Link Voltage16-32 Brake Energy / sFC 300 Design GuideHow to Programmefactory setting () display text [] value for use in communication via serial communication port194 MG.33.B7.02 - VLT is a registered Danfoss trademark