5.5.3 Relay Output D frameRelay 1• Terminal 01: common• Terminal 02: normal open 400 V AC• Terminal 03: normal closed 240 V ACRelay 2• Terminal 04: common• Terminal 05: normal open 400 V AC• Terminal 06: normal closed 240 V ACRelay 1 and relay 2 are programmed in 5-40 Function Relay,5-41 On Delay, Relay, and 5-42 Off Delay, Relay.Additional relay outputs by using option module MCB 105.130BC554.10relay1relay20302240Vac, 2A01060504240Vac, 2A400Vac, 2A400Vac, 2AIllustration 5.100 D-frame Additional Relay Outputs5.5.4 Relay Output E & F-FrameRelay 1• Terminal 01: common• Terminal 02: normal open 240 V AC• Terminal 03: normal closed 240 V ACRelay 2• Terminal 04: common• Terminal 05: normal open 400 V AC• Terminal 06: normal closed 240 V ACRelay 1 and relay 2 are programmed in 5-40 Function Relay,5-41 On Delay, Relay, and 5-42 Off Delay, Relay.Additional relay outputs by using option module MCB 105.relay1relay20302240Vac, 2A240Vac, 2A400Vac, 2A01060504130BA047.10Illustration 5.101 E- and F-frame Additional Relay Outputs5.6 Final Set-Up and TestTo test the set-up and ensure that the frequency converteris running, follow these steps.Step 1. Locate the motor name plate.NOTEThe motor is either star- (Y) or delta- connected (Δ). Thisinformation is on the motor name plate data.Step 2. Enter the motor name plate data in this parameterlist.To access this list, first press [Quick Menu], then select “Q2Quick Setup”.1. 1-20 Motor Power [kW] or 1-21 Motor Power [HP]2. 1-22 Motor Voltage3. 1-23 Motor Frequency4. 1-24 Motor Current5. 1-25 Motor Nominal SpeedHow to Install VLT® AQUA Drive FC 202 Design GuideMG20Z102 - VLT® is a registered Danfoss trademark 1475 5