P630 P710 P800 P900 P1M0 P1M2 P1M4Normal LoadTypical Shaft output at 550 V [kW] 500 560 670 750 850 1000 1100Typical Shaft output at 575 V [hp] 650 750 950 1050 1150 1350 1550Typical Shaft output at 690 V [kW] 630 710 800 900 1000 1200 1400Enclosure IP00 E2Enclosure IP21 E1 F1/F3 F1/F3 F1/F3 F2/F4 F2/F4 F2/F4Enclosure IP54 E1 F1/F3 F1/F3 F1/F3 F2/F4 F2/F4 F2/F4Output currentContinuous (at 550 V) [A] 630 763 889 988 1108 1317 1479Intermittent (60 s overload) (at 550 V)[A]693 839 978 1087 1219 1449 1627Continuous (at 575/690 V) [A] 630 730 850 945 1060 1260 1415Intermittent (60 s overload) (at 575/690V) [kVA]693 803 935 1040 1166 1386 1557Continuous kVA (at 550 V) [kVA] 600 727 847 941 1056 1255 1409Continuous kVA (at 575 V) [kVA] 627 727 847 941 1056 1255 1409Continuous kVA (at 690 V) [kVA] 753 872 1016 1129 1267 1506 1691Max. Input currentContinuous (at 550 V) [A] 607 743 866 962 1079 1282 1440Continuous (at 575 V) [A] 607 711 828 920 1032 1227 1378Continuous (at 690 V) [A] 607 711 828 920 1032 1227 1378Max cable sizeMotor (mm2/AWG2) )4x240(4x500mcm)8x150(8x300 mcm)12x150(12x300 mcm)Mains (mm2/AWG2) ) 8x240(8x500 mcm)8x240(8x500 mcm)Loadsharing (mm2/AWG2)) 4x185(4x350 mcm)6x185(6x350 mcm)Brake (mm2/AWG2)) 2x185(2x350mcm)Max. external mains fuses [A] 900 1600 1600 1600 1600 2000 2500Estimated power loss at 575 V [W] 3) 8209 9500 10872 12316 13731 16190 18536Estimated power loss at 690 V [W] 3) 8495 9863 11304 12798 14250 16821 19247Weight, enclosure IP20, IP21, IP54 kg(lbs.) 125 (275)Efficiency 4) 0.98Output frequency [Hz] 0–525Heatsink overtemp. trip [°C] 110 95 105 95 105 95Power card ambient trip [°C] 85Table 3.5 Mains Supply 3x525-690 V AC1) For type of fuse, consult the Operating Instructions.2) American Wire Gauge.3) The typical power loss is at normal conditions and expected to be within±15% (tolerance relates to variety in voltage and cable conditions.)These values are based on a typical motor efficiency (eff2/eff3 border line). Lower efficiency motors add to the power loss in the frequencyconverter and the opposite is also true. If the switching frequency is raised from nominal, the power losses rise significantly. LCP and typicalcontrol card power consumptions are included. Further options and customer load can add up to 30 W to the losses (though typically only 4 Wextra for a fully loaded control card or options for slot A or slot B, each).4) Measured using 5 m screened motor cables at rated load and rated frequency.Selection VLT® AQUA Drive FC 202 Design Guide44 MG20Z102 - VLT® is a registered Danfoss trademark33