Mechanical dimensionsEnclosure size [kW] D1h D2h D3h* D4h* E1 E2* F1 F2 F3 F4380–480 V AC525–690 V AC110–16045-160200–315200–400110–16045–160200–315200–400315–450450–630315–450450–630500–710710–900800–10001000–1400500–710710–900800–10001000–1400IPNEMA21/54Type 1/1221/54Type 1/1220Chassis20Chassis21/54Type 1/1200Chassis21/54Type 1/1221/54Type 1/1221/54Type 1/1221/54Type 1/12Shipping dimensions [mm]Width 997 1,170 997 1,170 2,197 1,705 2,324 2,324 2,324 2,324Height 587 587 587 587 840 831 1,569 1,962 2,159 2,559Depth 460 535 460 535 736 736 927 927 927 927Frequency Converter dimensions [mm]HeightA 901 1107 909 1122 2000 1547 2281 2281 2281 2281WidthB 325 420 250 350 600 585 1400 1800 2000 2400DepthC 380 380 375 375 494 494 607 607 607 607Dimensions brackets [mm/inch]Centre hole to back edge aNot Applicable56/2.2 23/0.9Centre hole to top edge b 25/1.0 25/1.0Hole diameter c 25/1.0 25/1.0Top of mounting slot tobottom edge d 27/1.1Width of mounting slot e 13/0.5Bottom mounting holefrom side edge f 63/2.5 75/3.0Not ApplicableBottom mounting holefrom bottom edge g 20/0.8 20/0.8Width of mounting slot h 11/0.4 11/0.4Bottom mounting holefrom side edge kNot Applicable25/1.0 40/1.6Not ApplicableheBottom mounting holefrom bottom edge l 20/0.8 20/0.8Width of mounting slot m 11/0.4 11/0.4Max weight [kg] 98 164 98 164 313 277 1017 1260 1318 1561Contact Danfoss for more detailed information and CAD drawings for your own planning purposes.*Chassis drives are intended for installation in external enclosuresTable 5.2 Legend to Table 5.1How to Install VLT® AQUA Drive FC 202 Design Guide88 MG20Z102 - VLT® is a registered Danfoss trademark55