I.B. 70A2580H02 Page 31Effective November 2012The recommendations and information containedherein are based on Eaton experience and judgment,but should not be considered to be all-inclusive orcovering every application or circumstance which mayarise. If further information is required, you shouldconsult Eaton.Testing Procedures: Assuming that the breaker issafely pulled out to the Test/Disconnect position in theenclosure or placed on the workbench, follow thisprocedure to perform the CloSure TM Test. For furtherinstructions on disconnecting the circuit breaker consultSection 4 of this manual. If the enclosure is equippedwith the MOC operating in the test position also, makecertain that the MOC is connected to operate.Step 1 - On the front cover identify the status indicators.MAKE SURE THE CLOSING SPRING STATUSINDICATES “Discharged” AND THE MAINCONTACT INDICATOR SHOWS “Open” (Figure 6-3).Step 2 - Remove the circuit breaker front cover. Be sureto save the original fasteners for reassembly.Step 3 - Cut a piece of one inch wide drafting/maskingtape approximately 8 to 10 inches long.Step 4 - Place the tape around the cam starting from thebottom up. Make certain that the tape adheres well tothe cam surface. (See Figures 6-4, 6-5 and 6-6).Step 5 - Mount the transparent CloSure TM Test Toolwith two bolts and washers. Refer to Figures 6-17, 6-18and Table 6.3 for appropriate mounting holes. Handtighten the bolts (Figures 6-7, 6-8, 6-17 and 6-18).Step 6 - A Sanford ® Sharpie ® black fine point permanentmarker, item no. 30001, is recommended for this nextstep. Place the marker tip in the proper hole (“C”). Referto Figure 6-17 and make a heavy mark on the tape asshown in Figure 6-10.Figure 6-6 Attaching Tape Around to Back of CamStep 7 - Charge the closing springs with themaintenance tool. Continue charging the closingsprings until a “click” is heard and the status indicatorshows “Charged” (Figure 6-9).Step 8 - While holding the marker tip on the tape,close the breaker (Figure 6-10).Step 9 - Move the marker back and forth horizontallyapproximately 15 o in both directions to create a lineon the tape that identifies the closed rest position(Figures 6-11, 6-12 and 6-13.Figure 6-7 Attaching CloSure TM Test Tool at Hole “A”Figure 6-8 Attaching CloSureTMTest Tool at HPole “B”Figure 6-9 Manually Charging Closing Springs