Eaton 93PM Integrated Battery Cabinet-Small (IBC-S) Installation Manual 164000305—Rev 06 3515. Route the battery cabinet ground wiring from the UPS through the bottom of the IBC to the IBC groundterminal block. See Figure 14 for terminal location.16. Connect the positive and negative power wiring to the IBC DC (+) and DC (-) output terminals. Connect theground wiring to the ground terminal on the IBC. See Table 5 for termination requirements.For a detailed view of the IBC terminal block, see Figure 16.17. Connect the positive, negative, and ground DC power wiring from the IBC or disconnect to the UPScabinet battery and ground terminals. Refer to the applicable Eaton 93PM UPS Installation and Operationmanual listed in paragraph 1.7 For More Information, for UPS cabinet termination requirements.NOTE If installing more than one IBC, individual conduit will be run between each batterycabinet and the UPS or disconnect. DO NOT run battery wiring from subsequent IBCsthrough the bottom of the adjacent IBCs.18. If installing more than one IBC, repeat Steps Step 12 through Step 17 for each IBC, and then proceed toparagraph 4.4 Installing IBC Interface Wiring; otherwise, proceed to paragraph4.4 Installing IBC Interface Wiring.NOTE Internal battery strings are to be connected by an authorized Eaton Customer ServiceEngineer at system startup.Figure 17. IBC-S Top and Bottom Entry Conduit and Wire Entry LocationsTop Entry ConduitLanding for DC Output(Remove panel to drillor punch conduit holes.)Bottom Entry ConduitLanding for DC Output(Remove panel to drillor punch conduit holes.)Top View Bottom View44..44 IInnssttaalllliinngg IIBBCC IInntteerrffaaccee WWiirriinnggIBCs can be installed in a line-up-and-match configuration with the interface wiring routed through the IBCs andUPS cabinet or in a standalone configuration with the interface wiring routed between the IBCs and the UPScabinet using conduit.Installation