40 Eaton 93PM Integrated Battery Cabinet-Small (IBC-S) Installation Manual 164000305—Rev 06Figure 20. Interface Terminal Detail – Eaton 93PM Integrated Battery Cabinet-SmallThermal SensorThermal Sensor ReturnNot UsedTo Next IBC TB2-2 (Battery Shunt Trip -)To Next IBC TB2-1 (Battery Shunt Trip +)To Next IBC TB2-4 (Battery Detect Common)Battery DetectNot UsedBattery Shunt Trip -Battery Shunt Trip +IBCTB244..44..22 IInnssttaalllliinngg BBaatttteerryy SShhuunntt TTrriipp IInntteerrffaaccee CCoonnnneeccttiioonnssNOTE 1 Disconnect terminal block plug from terminal block to wire plug.NOTE 2 Because of the battery shunt trip wiring route in the 93PM UPS cabinet, the wiring fromthe IBC shunt trip terminals to the UPS must use wire rated for 600V and Class 1 wiringmethods.NOTE 3 If the inter-cabinet wiring access pass-through is not used to install the battery shunt tripinterface wiring connections, conduit must be installed between the battery cabinet andthe UPS cabinet.To install wiring:1. If wiring the IBC shunt trip interface terminals using the line-up-and-match inter-cabinet wiring accesspass-through (see Figure 10) proceed to Step 2; if wiring the IBC shunt trip interface terminals using thetop entry access, proceed to Step 5; if wiring the IBC shunt trip interface terminals using the bottom entryaccess, proceed to Step 8.NOTE In multiple IBC installations, route the battery interface wiring between IBCs through thetop of the adjacent IBC using the top inter-cabinet access pass-through (see Figure 10).2. Line-Up-and-Match Wiring. Route the battery shunt trip interface wiring from the UPS battery shunt tripinterface terminals through the bottom inter-cabinet access pass-through (see Figure 10) of the UPScabinet and IBC to the wiring channel on the left side of the IBC (see Figure 13). Route the wiring along thewiring channel to the IBC battery interface terminal block TB2. See Figure 18 for terminal locations. SeeTable 7, and Figure 19 for wiring and termination requirements. Refer to the applicable Eaton 93PM UPSInstallation and Operation manual listed in paragraph 1.7 For More Information, for UPS cabinet terminallocations.3. Secure the interface wiring to the wire tie anchors (see Figure 15) using Zip ties.4. Proceed to Step 11.Installation